Passivt brannslokkingsutstyr, brannhydrant (BLIX)

KU-BRO-0000-22

3 måneders intervall

Aktivitetsnummer: 1000

Oppgavebeskrivelse

Påse at brannhydranten, inkl. åpne-/lukkemutter og utløp/koblinger, er fri for lekkasje (vann og is), smuss, korrosjon, skader og slitasje. Påse at tilgjengelighet, merking og skilting er i orden. Rengjøres, og evt. males om, ved behov.

Kommentar

Dok.ref: Underground Hydrant EN14339 MODEL “VOLCAN” – UFB-30-A-
65536 Follobanen, Blixtunnelen og Åsland, Elektro lavspenning,
Brannsikkerhetssystemer, FDV brukerhåndbok, Km 2,050 –
22,384 ¿[R6]

According to UFB-30-Q-65502 The Follo Line Project, EPC TBM. 
FMECA Report for the Fire Water System ¿[R3]:
- Section 5.2. Overview of preventive maintenance activities with 
optimized intervals.
- Section 6. FMECA (RESULT):
o 3.1 and 3.2 Underground Fire hydrants, with two outlets 
ø70 mm
o 4.1 and 4.2 NOR couplings for firefighting hose

Kommentar:  
Interval after the first year must be adjusted according to experience. 
  • Intervall 3 md
  • Myndighetsnivå Lav
  • Type FV TK-V

Aktivitetsnummer: 1010

Oppgavebeskrivelse

Påse at hydrantventilen er lukket. Påse at hettene over koblingene lett kan fjernes og at kjedene er slik at hettene lett kan dreies.

Kommentar

Dok.ref: Underground Hydrant EN14339 MODEL “VOLCAN” – UFB-30-A-
65536 Follobanen, Blixtunnelen og Åsland, Elektro lavspenning,
Brannsikkerhetssystemer, FDV brukerhåndbok, Km 2,050 –
22,384 ¿[R6]

According to UFB-30-Q-65502 The Follo Line Project, EPC TBM. 
FMECA Report for the Fire Water System ¿[R3]:
- Section 5.2. Overview of preventive maintenance activities with 
optimized intervals.
- Section 6. FMECA (RESULT):
o 3.1 and 3.2 Underground Fire hydrants, with two outlets 
ø70 mm
o 4.1 and 4.2 NOR couplings for firefighting hose

Kommentar: 
Interval after the first year must be adjusted according to experience. 
  • Intervall 3 md
  • Myndighetsnivå Lav
  • Type FV TK-V

6 måneders intervall

Aktivitetsnummer: 1020

Oppgavebeskrivelse

Demonter hydrantventilen og smør spindelgjengene og åpne-/lukkemutteren. Luft hydranten etter montasje, og påse at hydranten er fri for lekkasjer i koblinger, flensforbindelser og tetninger. Påse at alle ventilene i nettverket er helt åpne.

Kommentar

Dok.ref: Underground Hydrant EN14339 MODEL “VOLCAN” – UFB-30-A-
65536 Follobanen, Blixtunnelen og Åsland, Elektro lavspenning,
Brannsikkerhetssystemer, FDV brukerhåndbok, Km 2,050 –
22,384 ¿[R6]

According to UFB-30-Q-65502 The Follo Line Project, EPC TBM. 
FMECA Report for the Fire Water System ¿[R3]:
- Section 5.2. Overview of preventive maintenance activities with 
optimized intervals.
- Section 6. FMECA (RESULT):
o 3.1 and 3.2 Underground Fire hydrants, with two outlets 
ø70 mm
o 4.1 and 4.2 NOR couplings for firefighting hose

Kommentar: 
To be performed together with the 3 month inspections

While disassembling/
maintenance is ongoing, the whole fire water system in the relevant tunnel is inoperable due to no gate valve that separates each hydrant, so compensating actions are needed. It is recommended that a spare hydrant is available to put into operation in the relevant tunnel where the hydrant is disassembled. The time estimated to overhaul the hydrant is unknown.

Maintenance interval is 6 months according to supplier recommendation, but an interval of 6 months the first year then every 36 months is recommended according to discussions with Company. 
  • Intervall 6 md
  • Myndighetsnivå Lav
  • Type FV PO

12 måneders intervall

Aktivitetsnummer: 1030

Oppgavebeskrivelse

Påse at strømning og trykk har korrekt foreskrevet verdi på det mest ugunstige punktet på nettet, ved aktivering av alle relevante hydranter i området.

Kommentar

Dok.ref: Underground Hydrant EN14339 MODEL “VOLCAN” – UFB-30-A-
65536 Follobanen, Blixtunnelen og Åsland, Elektro lavspenning,
Brannsikkerhetssystemer, FDV brukerhåndbok, Km 2,050 –
22,384 ¿[R6]

According to UFB-30-Q-65502 The Follo Line Project, EPC TBM. 
FMECA Report for the Fire Water System ¿[R3]:
- Section 5.2. Overview of preventive maintenance activities with 
optimized intervals.
- Section 6. FMECA (RESULT):
o 3.1 and 3.2 Underground Fire hydrants, with two outlets 
ø70 mm

 Kommentar:
Proposed routine and intervals as a result of workshop 18.06.21.

To be performed together with visual inspection of pipes. Interval after the first year must be adjusted according to experience. 
  • Intervall 12 md
  • Myndighetsnivå Lav
  • Type FV TK-V