Public Key Infrastructure i KMC og PKI kabinett ERTMS
SA-RAC-0000-04
1 måneders intervall
Oppgave | Oppgavebeskrivelse | Lang-beskrivelse | Intervall | Myndighetsnivå | Type FV |
---|---|---|---|---|---|
1000 | Maintenance of smart cards |
Ensure enough smart card sets are available for personel to restore the Root CA in case it is needed. Copy smart cards by following the procedure in the manual. See doc. 2000001593 "Maintenance Instructions Public Key Infrastructure - Certificate Authority" chapter 7.6 "Maintenance of smart cards" on page 185 for procedure. |
1 md | Høy | TK-V |
Oppgave: 1000
Oppgavebeskrivelse
Maintenance of smart cardsLang-beskrivelse
Ensure enough smart card sets are available for personel to restore the Root CA in case it is needed. Copy smart cards by following the procedure in the manual.See doc. 2000001593 "Maintenance Instructions Public Key Infrastructure
- Certificate Authority" chapter 7.6 "Maintenance of smart cards" on page 185 for procedure.
- Intervall 1 md
- Myndighetsnivå Høy
- Type FV TK-V
12 måneders intervall
Oppgave | Oppgavebeskrivelse | Lang-beskrivelse | Intervall | Myndighetsnivå | Type FV |
---|---|---|---|---|---|
1010 | Visual inspection of the cleanliness of computer cabinet and components |
Check whether the cabinet and its components are clean and undamaged. Se dok. 2000006700 "Operating and Service Manual Generic Master CCF Cabinets" kap 8.3.1 "Visual inspection of the cleanliness of computer cabinet and components" på side 67 for prosedyre. |
12 md | Høy | TK-V |
1020 | Functional test of computer cabinet doors |
Check whether the cabinet doors close easily and tightly. Se dok. 2000006700 "Operating and Service Manual Generic Master CCF Cabinets" kap 8.3.2 "Functional test of computer cabinet doors" på side 67 for prosedyre. |
12 md | Høy | TK-F |
1030 | Visual inspection of cables and connectors |
1) Check whether the earthing cables are connected from the cabinet doors to the cabinet frame. 2) Check whether the earthing cable of the cabinet is fixed and not torn off. 3) Check whether the contact clips and cable straps are fixed properly. 4) Check whether the incoming and outgoing cables are laid and fixed properly. 5) Check whether all connectors are plugged in properly, fixed and labeled. Se dok. 2000006700 "Operating and Service Manual Generic Master CCF Cabinets" kap 8.3.3 "Visual inspection of cables and connectors" på side 68 for prosedyre. |
12 md | Høy | TK-V |
1040 | Visual inspection of CoolBlastT 230V HP fan assembly |
1) Check whether the fan assembly is operational: the green LED “system ok” on the front of the fan must light up. 2) Check that the fan speed operates in the required range: the red LED on the front of the fan is off. 3) Check whether the fan assembly is making unusual noises. Se dok. 2000006700 "Operating and Service Manual Generic Master CCF Cabinets" kap 8.3.3 "Visual inspection of CoolBlastT 230V HP fan assembly" på side 68 for prosedyre. |
12 md | Høy | TK-V |
1050 | Visual inspection of AC115-230V/DC24V fan assembly |
1) Check whether the fan assembly is operational: the green LED on the front of the fan must light up. 2) Check that the fan speed operates in the required range: the red LED on the front of the fan is off. 3) Check whether the fan assembly is making unusual noises. Se dok. 2000006700 "Operating and Service Manual Generic Master CCF Cabinets" kap 8.3.3 "Visual inspection of cables and connectors" på side 69 for prosedyre. |
12 md | Høy | TK-V |
1060 | Functional test of AC115-230V/DC24V fan assembly |
Press the blue button. The red LED must light up. Se dok. 2000006700 "Operating and Service Manual Generic Master CCF Cabinets" kap 8.3.3 "Functional test of AC115-230V/DC24V fan assembly" på side 70 for prosedyre. |
12 md | Høy | TK-F |
Oppgave: 1010
Oppgavebeskrivelse
Visual inspection of the cleanliness of computer cabinet and componentsLang-beskrivelse
Check whether the cabinet and its components are clean and undamaged.Se dok. 2000006700 "Operating and Service Manual Generic
Master CCF Cabinets" kap 8.3.1 "Visual inspection of the cleanliness of computer cabinet and components" på side 67 for prosedyre.
- Intervall 12 md
- Myndighetsnivå Høy
- Type FV TK-V
Oppgave: 1020
Oppgavebeskrivelse
Functional test of computer cabinet doorsLang-beskrivelse
Check whether the cabinet doors close easily and tightly.Se dok. 2000006700 "Operating and Service Manual Generic
Master CCF Cabinets" kap 8.3.2 "Functional test of computer cabinet doors" på side 67 for prosedyre.
- Intervall 12 md
- Myndighetsnivå Høy
- Type FV TK-F
Oppgave: 1030
Oppgavebeskrivelse
Visual inspection of cables and connectorsLang-beskrivelse
1) Check whether the earthing cables are connected from the cabinet doors to the cabinet frame.2) Check whether the earthing cable of the cabinet is fixed and not torn off.
3) Check whether the contact clips and cable straps are fixed properly.
4) Check whether the incoming and outgoing cables are laid and fixed properly.
5) Check whether all connectors are plugged in properly, fixed and labeled.
Se dok. 2000006700 "Operating and Service Manual Generic
Master CCF Cabinets" kap 8.3.3 "Visual inspection of cables and connectors" på side 68 for prosedyre.
- Intervall 12 md
- Myndighetsnivå Høy
- Type FV TK-V
Oppgave: 1040
Oppgavebeskrivelse
Visual inspection of CoolBlastT 230V HP fan assemblyLang-beskrivelse
1) Check whether the fan assembly is operational: the green LED “system ok” on the front of the fan must light up.2) Check that the fan speed operates in the required range: the red LED on the front of the fan is off.
3) Check whether the fan assembly is making unusual noises.
Se dok. 2000006700 "Operating and Service Manual Generic
Master CCF Cabinets" kap 8.3.3 "Visual inspection of CoolBlastT 230V HP fan assembly" på side 68 for prosedyre.
- Intervall 12 md
- Myndighetsnivå Høy
- Type FV TK-V
Oppgave: 1050
Oppgavebeskrivelse
Visual inspection of AC115-230V/DC24V fan assemblyLang-beskrivelse
1) Check whether the fan assembly is operational: the green LED on the front of the fan must light up.2) Check that the fan speed operates in the required range: the red LED on the front of the fan is off.
3) Check whether the fan assembly is making unusual noises.
Se dok. 2000006700 "Operating and Service Manual Generic
Master CCF Cabinets" kap 8.3.3 "Visual inspection of cables and connectors" på side 69 for prosedyre.
- Intervall 12 md
- Myndighetsnivå Høy
- Type FV TK-V
Oppgave: 1060
Oppgavebeskrivelse
Functional test of AC115-230V/DC24V fan assemblyLang-beskrivelse
Press the blue button. The red LED must light up.Se dok. 2000006700 "Operating and Service Manual Generic
Master CCF Cabinets" kap 8.3.3 "Functional test of AC115-230V/DC24V fan assembly" på side 70 for prosedyre.
- Intervall 12 md
- Myndighetsnivå Høy
- Type FV TK-F