Batteri (18kVA, 54kVA, 108kVA) (SKI)
EL-BAT-0000-08
6 måneders intervall
Aktivitetsnummer: 1000
Oppgavebeskrivelse
Påse at batteri er fulladet.Kommentar
System control and adjustment
Calibration of AC and DC output voltage:
Check that the AC and DC voltages are correct.
If they deviate more than + - 1% - calibrate this value.
AC and DC load anbad battery power control:
Measure with an ampere meter that all currents are correct on the display in relation to the measured value.
If the measured value deviates more than + - 2% from what the display shows - calibrate this value.
DC output voltage control:
Measure the DC voltage on the DC distribution with a little load connected. If this voltage on the display deviates more than 1% from the measured value - calibrate this value.
Alarm relay test:
Connect the PC and run the alarm relay output test to check all the alarm relays.
For the battery bank check: The LI-Ion battery will run this control even via BSM
Manual bypass function:
Follow the procedure for manual bypass switch and enable / disable bypass switch
Dokumentreferanse
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, UOS-90-A-56106_01D, UOS-90-A-56108_01D, UOS-90-A-56118_01D, UOS-90-A-56126_01D- Intervall 6 md
- Myndighetsnivå Lav
- Type FV TK-M
Aktivitetsnummer: 1010
Oppgavebeskrivelse
Påse at batterisystemet er rent, i orden, fri for skader og slitasje.Kommentar
System control and adjustment
Calibration of AC and DC output voltage:
Check that the AC and DC voltages are correct.
If they deviate more than + - 1% - calibrate this value.
AC and DC load anbad battery power control:
Measure with an ampere meter that all currents are correct on the display in relation to the measured value.
If the measured value deviates more than + - 2% from what the display shows - calibrate this value.
DC output voltage control:
Measure the DC voltage on the DC distribution with a little load connected. If this voltage on the display deviates more than 1% from the measured value - calibrate this value.
Alarm relay test:
Connect the PC and run the alarm relay output test to check all the alarm relays.
For the battery bank check: The LI-Ion battery will run this control even via BSM
Manual bypass function:
Follow the procedure for manual bypass switch and enable / disable bypass switch
Dokumentreferanse
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, UOS-90-A-56106_01D, UOS-90-A-56108_01D, UOS-90-A-56118_01D, UOS-90-A-56126_01D- Intervall 6 md
- Myndighetsnivå Lav
- Type FV TK-V
Aktivitetsnummer: 1020
Oppgavebeskrivelse
Påse at koblingene til batteribanken er ordentlig tilskrudd, og at batteriene og batteripolene er fri for lekkasjer.Kommentar
System control and adjustment
Calibration of AC and DC output voltage:
Check that the AC and DC voltages are correct.
If they deviate more than + - 1% - calibrate this value.
AC and DC load anbad battery power control:
Measure with an ampere meter that all currents are correct on the display in relation to the measured value.
If the measured value deviates more than + - 2% from what the display shows - calibrate this value.
DC output voltage control:
Measure the DC voltage on the DC distribution with a little load connected. If this voltage on the display deviates more than 1% from the measured value - calibrate this value.
Alarm relay test:
Connect the PC and run the alarm relay output test to check all the alarm relays.
For the battery bank check: The LI-Ion battery will run this control even via BSM
Manual bypass function:
Follow the procedure for manual bypass switch and enable / disable bypass switch
Dokumentreferanse
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, UOS-90-A-56106_01D, UOS-90-A-56108_01D, UOS-90-A-56118_01D, UOS-90-A-56126_01D- Intervall 6 md
- Myndighetsnivå Lav
- Type FV TK-V
Aktivitetsnummer: 1030
Oppgavebeskrivelse
Påse at batteribanken fungerer som den skal, ved å gjøre en batteriutladningstest.Kommentar
System control and adjustment
Calibration of AC and DC output voltage:
Check that the AC and DC voltages are correct.
If they deviate more than + - 1% - calibrate this value.
AC and DC load anbad battery power control:
Measure with an ampere meter that all currents are correct on the display in relation to the measured value.
If the measured value deviates more than + - 2% from what the display shows - calibrate this value.
DC output voltage control:
Measure the DC voltage on the DC distribution with a little load connected. If this voltage on the display deviates more than 1% from the measured value - calibrate this value.
Alarm relay test:
Connect the PC and run the alarm relay output test to check all the alarm relays.
For the battery bank check: The LI-Ion battery will run this control even via BSM
Manual bypass function:
Follow the procedure for manual bypass switch and enable / disable bypass switch
Dokumentreferanse
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, UOS-90-A-56106_01D, UOS-90-A-56108_01D, UOS-90-A-56118_01D, UOS-90-A-56126_01D- Intervall 6 md
- Myndighetsnivå Lav
- Type FV TK-F
Aktivitetsnummer: 1040
Oppgavebeskrivelse
Påse at kabler, koblinger og fordelingsskinner har god kontakt.Kommentar
System control and adjustment
Calibration of AC and DC output voltage:
Check that the AC and DC voltages are correct.
If they deviate more than + - 1% - calibrate this value.
AC and DC load anbad battery power control:
Measure with an ampere meter that all currents are correct on the display in relation to the measured value.
If the measured value deviates more than + - 2% from what the display shows - calibrate this value.
DC output voltage control:
Measure the DC voltage on the DC distribution with a little load connected. If this voltage on the display deviates more than 1% from the measured value - calibrate this value.
Alarm relay test:
Connect the PC and run the alarm relay output test to check all the alarm relays.
For the battery bank check: The LI-Ion battery will run this control even via BSM
Manual bypass function:
Follow the procedure for manual bypass switch and enable / disable bypass switch
Dokumentreferanse
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, UOS-90-A-56106_01D, UOS-90-A-56108_01D, UOS-90-A-56118_01D, UOS-90-A-56126_01D- Intervall 6 md
- Myndighetsnivå Lav
- Type FV TK-V