Brytere og skillebrytere (SKI)

EH-BRY-0000-11

12 måneders intervall

Oppgave Oppgavebeskrivelse Lang-beskrivelse Dokumentreferanse Intervall Myndighetsnivå Type FV
1000 Påse at kontaktene er fri for forurensing. Rengjør ved behov.
Use solvent or degreaser if necessary.

Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56009 12 md Lav TK-V
1010 Smør kontaktene med et tynt lag Barrierta L55 / 1.
Apply a very thin layer of lubrication Barrierta L55 / 1 (from the company Klüber Lubrication) on the contacts.

Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56009 12 md Lav TK-VE
1020 Påse at alle lager og ledd beveger seg lett. Smør med Rivolta S.K.D 16 N (Bremern & Leguil).
Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56010 12 md Lav TK-F
1030 Påse at festeboltene og tilkoblingsskruene til kontrollmekanismen er i orden og fri for skader.
Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56011 12 md Lav TK-M
1040 Rengjør isolatorene.
Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.
Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56012 12 md Lav TK-M

Oppgave: 1000

Oppgavebeskrivelse

Påse at kontaktene er fri for forurensing. Rengjør ved behov.

Lang-beskrivelse

Use solvent or degreaser if necessary.

Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.

Dokumentreferanse

Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56009
  • Intervall 12 md
  • Myndighetsnivå Lav
  • Type FV TK-V

Oppgave: 1010

Oppgavebeskrivelse

Smør kontaktene med et tynt lag Barrierta L55 / 1.

Lang-beskrivelse

Apply a very thin layer of lubrication Barrierta L55 / 1 (from the company Klüber Lubrication) on the contacts.

Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.

Dokumentreferanse

Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56009
  • Intervall 12 md
  • Myndighetsnivå Lav
  • Type FV TK-VE

Oppgave: 1020

Oppgavebeskrivelse

Påse at alle lager og ledd beveger seg lett. Smør med Rivolta S.K.D 16 N (Bremern & Leguil).

Lang-beskrivelse

Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.

Dokumentreferanse

Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56010
  • Intervall 12 md
  • Myndighetsnivå Lav
  • Type FV TK-F

Oppgave: 1030

Oppgavebeskrivelse

Påse at festeboltene og tilkoblingsskruene til kontrollmekanismen er i orden og fri for skader.

Lang-beskrivelse

Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.

Dokumentreferanse

Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56011
  • Intervall 12 md
  • Myndighetsnivå Lav
  • Type FV TK-M

Oppgave: 1040

Oppgavebeskrivelse

Rengjør isolatorene.

Lang-beskrivelse

Maintenance work is largely limited to cleaning and lubricating the contacts, bearing points in the frame and cleaning of insulating parts. If the silver coating on the main circuit and the shunt circuit become hot over prolonged use, these must be replaced immediately.
Outdoor circuit breakers must be inspected after each short-circuit connection operation.Maintenance or repair work may be required due to unusual load.
Connection Operation
When the hinged insulator is moved in the connection direction, the contact arm moves with the contact plates enter the switch fork in the arc chamber.
Upon further movement, a spring-loaded mechanism inside the arc chamber will be activated, somewhat which turns on the vacuum switch.
Full current on the main contacts is not guaranteed until the end position is reached. In operating mode, the vacuum switch is bypassed.
During disconnection operation, the main contacts are first broken so that the current is fully connected with bypassed vacuum switch via the contact arm. When the disconnection operation continues, opens the vacuum switch in the arc chamber and switches the electricity. The OFF mode is then achieved when the contact system is at the correct, insulating distance. There are no external arcs visible during the switch operations.

Dokumentreferanse

Østfoldbanen V L (Oslo S) - Ski, Ski Stasjon, Elektro høyspent, Kontaktledningsanlegg, FDV Brukerhåndbok, Km 22,400 - 25,880, UOS-90-56012
  • Intervall 12 md
  • Myndighetsnivå Lav
  • Type FV TK-M